ERDA1
ERDA1 ENDA Product
  • 25 and 40A AC load current

  • 320V AC or 480V AC load voltage

  • 8-30V AC/DC input voltage

  • LED status indicator for input voltage

  • Zero-cross switching

  • Applicable for three phase loads

  • Built-in varistor protection

  • CE marked according to European Norms

Manuals

Environmental Conditions
Ambient/Storage Temperature -25...60 ºC / -30...100 ºC
Relative Humidity 90% relative humidity for temperatures up to 20 °C, decreasing linearly to 50% at 40 °C
Protection Degree According to EN 60529 IP20
Height Max. 1000m
Electrical Characteristics
Input Voltage 8-30V AC/DC
Pick-up Voltage >6V AC/DC
Drop-out Voltage ˂2V AC/DC
Input Current ˂17mA AC/10mA DC
Turn-on Time Max. ½ Period
Turn-off Time Max. ½ Period
LED Indicator If the input voltage ˃6V AC/DC then LED lit
Load Current (Arms) ERDA1-225Z: 25
ERDA1-240Z: 40
ERDA1-425Z: 25
ERDA1-440Z: 40

Load Voltage (Vrms) ERDA1-225Z and ERDA1-240Z: 24-320
ERDA1-425Z and ERDA1-440Z: 50-480

Frequency (Hz) 50-60
Housing
Mounting Method TH35 rail mounting
Dimensions ERDA1-225Z and ERDA1-425Z: W24xYH84xD97 mm
ERDA1-240Z and ERDA1-440Z: W30xYH84xD115 mm

Weight ERDA1-225Z and ERDA1-425Z: 203g (after packaging)
ERDA1-240Z ve ERDA1-440Z: 280g (after packaging)

Enclosure Material Self extinguishing plastics
Please choose your preferred language.