Input Type
If the ityp parameter set to u500, 0...500V AC/DC input is used for 0...500V AC/DC scale measurement
If the ityp parameter set to u100, 0...100V AC/DC input is used for 0...100V AC/DC scale measurement
If the ityp parameter set to utrr, 0-100V AC/DC input is used with voltage transformer measurement and utrr parameter determines the scale
Scale
AC and RMS:
If the ityp parameter set to u500, the scale range is 0...500V AC/DC.
If the ityp parameter set to u100, the scale range is 0...100V AC/DC
If the ityp parameter set to utrr, the scale range is 0-9999V AC/DC (utrr parameter determines the scale. ie: scale range will be -999...1000V if the utrr parameter is set to 1000)
DC:
If the ityp parameter set to u500, the scale range is -500...500V DC
If the ityp parameter set to u100, the scale range is -100...100V DC
If the ityp parameter set to utrr, the scale range is -9999-9999V DC (utrr parameter determines the scale. ie: scale range will be -999...1000V if the utrr parameter is set to 1000)
Accuracy
AC: ±1%(of full scale) (±2% for square wave form)
DC: ±1% (of full scale)
RMS: ±1% (of full scale) (±2% for square wave form)
Input Range
0...500V AC/DC (device will be damaged if more than ±1250 DC voltages applied)
0...100V AC/DC (device will be damaged if more than ±250 DC voltages applied)
Input Impedance
For 0-500V input 880kohm
For 0-100V input 177kohm
Frequency Range
AC , 10Hz-200Hz (10Hz-70Hz for square wave form)
Supply
ECVC-UV: 90-250V AC, 50/60Hz
ECVC-LV: 10-30V DC or 8-24V AC, 50/60Hz
Power Consumption
Max. 7VA
Outputs
mA: 0-20mA DC or 4-20mA DC, ±0,5% (load resistance max. 500ohm)
V: 0-10V DC or 1-5V DC, max.10mA, ±0,5% (Short circuit protected)
External Connections
Plug-in terminals