Input Type
For ECCC-xV 5A or 60mV
For ECCC-CT-xV CT20/30 current transformer or 60mV
For ECCC-X1-xV 1A
Scale
AC and RMS:
Input type 5A/60mV: 0...9999A (specified by c.tr.r parameter)
For example: If c.tr.r=5, scale is 0...5A
Input type CT20/30 or 60mV:
If itYP=Ct20, input range is 0...300A (specified by turn parameter)
For example: If turn=1, scale is 0...300A
itYP=Ct30, input range is 0...120A (specified by tUrn parameter)
For example: If turn=1, scale is 0...120A
Input type 1A: 0...9999A (specified by c.tr.r parameter)
For example: If c.tr.r=1, scale is 0...1A
DC:
Input type 5A/60mV: -999...9999A (specified by c.t.r.r parameter)
For example: If c.tr.r=5, scale is -5...5A
Input type CT20/30/60mV :
DC Measurement can not be performed by using current transformer
If itYP=SHnt, input range is -999..9999A (specified by c.tr.r parameter)
For example: If c.tr.r=5, scale is -5...5A
Input type 1A : -999...9999A (specified by c.t.r.r parameter)
For example: c.tr.r=1 için scale -1...1A
Sensitivity
0.002A x c.t.r.r (for example, 0.01A for c.t.r.r=5)
Accuracy
AC: ±1%(of full scale) (±2% for square wave form)
DC: ±1% (of full scale)
RMS: ±1% (of full scale) (±2% for square wave form)
Input Range
Input type 60mV: -60mV...60mV (device may be damaged at 50V and above voltages)
Input type 1A: -1A...1A (device may be damaged at 2A and above currents)
Input type 5A: -5A...5A (device may be damaged at 10A and above currents)
Input type CT20/30 : 0...150mA
Input Impedance
Input type 60mV: 20kohm
Input type 1A: 90mohm
Input type 5A: 12mohm
Input type CT20/30: 600mohm
Frequency Range
DC, 20Hz - 70Hz
Supply
ECCC411-UV: 90-250V AC, 50/60Hz
ECCC411-LV: 10-30V DC or 8-24V AC, 50/60Hz
Power Consumption
Max. 7VA
Outputs
mA: 0-20mA DC or 4-20mA DC, ±0,5% (load resistance max. 500Ω)
V: 0-10V DC or 1-5V DC, max.10mA, ±0,5% (Short circuit protected)
External Connections
Plug-in terminals