NTC or J type thermocouple inputs (order option)
Indicates NTC input decimal
Offset feature for input
C1 relay out for temperature control
When C1 output configuration is selected for cooling, compressor delay time can be entered
Selectable heating/cooling control
In case of sensor failure, relay state can be configured as On or Off
CE marked according to European Norms
Environmental Conditions | |
Ambient/Storage Temperature | 0...50 ºC / -25...70 ºC |
Relative Humidity | 80% relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C |
Protection Degree | According to EN 60529 Front panel: IP62, Rear panel: IP20 |
Height | Max. 2000m |
Electrical Characteristics | |
Supply | 230V AC +10% -20% 50/60Hz or 12/24V AC/DC ±10% |
Power Consumption | 5VA |
External Connections | Screw-terminals |
Scale | Fe-Const (J) thermocouple -30...400 °C, NTC probe -25.0...110.0 °C |
Accuracy | ± 1% (of full scale) ± 1 digit |
Line Resistance | Max. 100ohm |
Output | |
C1 Output | 5A model: 250V AC, 5A (for resistive load), NO control output 8A model: 250V AC, 8A (for resistive load), NO+NC control output 16A model: 250V AC, 16A (for resistive load), NO control output |
Life Expectancy | 5A model: Mechanical 5.000.000 operations (under no load), Electrical 100.000 operations (5A at 250V AC, resistive load) 8A model: Mechanical 30.000.000 operations (under no load), Electrical 300.000 operations (8A at 250V AC, resistive load) 16A model: Mechanical 30.000.000 operations (under no load), Electrical 100.000 operations (16A at 250V AC, resistive load) |
Control | |
Control Type | Single-setpoint control |
Control Algorithm | On-Off |
A/D converter | 12 bit |
Sampling Time | 100ms |
Hysteresis | Adjustable between 0.1 and 5.0 °C |
Housing | |
Mounting Method | Panel mounting |
Dimensions | W77xH35xD61 mm |
Weight | Approx. 215g (after packaging) |
Enclosure Material | Self extinguishing plastics |