On-off control
Decimal indication
3 outputs for fan and air conditioning control
On-off cooling control for air conditioning (AC)
Fan and air conditioning control via keypad manually
CE marked according to European Norms
Environmental Conditions | |
Ambient/Storage Temperature | 0...50 ºC / -25...70 ºC |
Relative Humidity | 80% relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C |
Protection Degree | According to EN 60529 Front panel: IP65, Rear panel: IP20 |
Height | Max. 2000m |
Electrical Characteristics | |
Supply | 230V AC +10% -20% 50/60Hz or 12/24V AC/DC ±10% |
Power Consumption | 4.5VA |
External Connections | Screw-terminals |
Scale | 0.0...150.0 °C |
Sensitivity | 0.1 °C |
Accuracy | ±1 °C |
Outputs | |
Circulation | Relay: 250V AC, 8A (for resistive load), NO; 1/2hp 240V AC Cosφ= 0.4 (for inductive load) |
Coal | Relay: 250V AC, 8A (for resistive load), NO+NC; 1/2hp 240V AC Cosφ= 0.4 (for inductive load) |
Fan2 | Relay: 250V AC, 8A (for resistive load), NO; 1/2hp 240V AC Cosφ= 0.4 (for inductive load) |
Life Expectancy | Mechanical 30.000.000 operations (under no load), Electrical 100.000 operations (8A at 250V AC, resistive load) |
Control | |
Control Type | Single set-point |
Control Algorithm | On-Off |
Hysteresis | 0.5 °C |
Housing | |
Mounting Method | Panel mounting |
Dimensions | W77xH35xD71 mm |
Weight | Approx. 223g (After packing) |
Enclosure Material | Self extinguishing plastics |