ET1413
  • 4 digits display

  • Decimal indication

  • 3 outputs for fan and air conditioning control

  • Fan and air conditioning control via keypad manually

  • CE marked according to European Norms

Manuals

Environmental Conditions
Ambient/Storage Temperature0...50 ºC / -25...70 ºC
Relative Humidity80% relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C
Protection DegreeAccording to EN 60529 Front panel: IP62, Rear panel: IP20
HeightMax. 2000m
Electrical Characteristics
Supply230V AC +10% -20% 50/60Hz or 12/24V AC/DC ±10%
Power Consumption4.5VA
External ConnectionsScrew-terminals
Scale-50.0...110.0 °C
Sensitivity0.1 °C
Accuracy±1 °C
Outputs
Air Conditioning (A/C)Relay: 250V AC, 8A (for resistive load), NO; 1/2hp 240V AC Cosφ= 0.4 (for inductive load)
Fan1Relay: 250V AC, 8A (for resistive load), NO+NC; 1/2hp 240V AC Cosφ= 0.4 (for inductive load)
Fan2Relay: 250V AC, 8A (for resistive load), NO; 1/2hp 240V AC Cosφ= 0.4 (for inductive load)
Life ExpectancyMechanical 30.000.000 operations (under no load), Electrical 100.000 operations (8A at 250V AC, resistive load)
Housing
Mounting MethodPanel mounting
DimensionsW77xH35xD71 mm
WeightApprox. 223g (After packing)
Enclosure MaterialSelf extinguishing plastics