EI2041
  • 4 digits display

  • Display scale can be adjusted between -1999 and 4000

  • Decimal point can be adjusted between 1. and 3. digits

  • Measurement unit can be displayed

  • Selectable four different standard input types (0-20mA, 4-20mA, 0-1V, 0-10V)

  • User can calibrate the device according to specified input type

  • Sampling time can be adjusted in four steps

  • Stores maximum and minimum measurement values

  • Two relay outputs for control and alarm (order option)

  • Above and below set point value can be set

  • Selectable independent, deviation and band alarm

  • Sensor supply output(Optional)

  • RS485 Modbus RTU communication protocol feature (order option)

  • CE marked according to European Norms

Manuals

Ambient/Storage Temperature0...50 ºC / -25...70 ºC
Relative Humidity80% Relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C
Protection DegreeAccording to EN 60529 Front panel:IP65, Rear panel:IP20
HeightMax. 2000m
Electrical Characteristics
Supply230/110V AC +10% -20% or 12/24V AC ±10%, 50/60Hz or 9-30V DC / 7-24V AC ±10% SMPS
Power Consumption7VA
External ConnectionsScrew-terminals
ScaleAdjustable between -1999...4000
Accuracy0-1V DC: ±0.5% (of full scale)
0-10V DC: ±0.5% (of full scale)
0-20mA DC: ±0.5% (of full scale)
4-20mA DC: ±0.5% (of full scale)
Measurement Range0-1V DC: Max. 1.1V
0-10V DC: Max. 12V
0-20mA DC: Max. 25mA
4-20mA DC: Max. 25mA
Input Empedance0-1V DC: Approx. 100kohm
0-10V DC: Approx. 100kohm
0-20mA DC: Approx. 10ohm
4-20mA DC: Approx. 10ohm
Outputs
Auxiliary Power SupplyAll sensor supply outputs maximum 50 mA (regulated and isolated)
Alarm Output2 Relays: 250V AC, 8A (for resistive load), NO
Life ExpectancyMechanical 30.000.000 operations (under no load), Electrical 100.000 operations (8A at 250V AC, resistive load)
Control
Control TypeDouble set-point and alarm control
Control AlgorithmOn-Off
HysteresisAdjustable between 1...200
Housing
Mounting MethodPanel mounting
DimensionsW77xH35xD61 mm
WeightApprox. 250g (after packaging)
Enclosure MaterialSelf extinguishing plastics
Looks like you don't speak Turkish. Would you like to view this content in English? Yes, please No