ESHT102-W
  • 0...100 RH% humidity measurement

  • -40...125 °C temperature measurement

  • Selectable 0-20mA or 0-10V output

  • Wall type mounting

  • CE marked according to European Norms

Manuals

Environmental Conditions
Ambient/Storage Temperature-40...60 ºC
Protection DegreeAccording to EN 60529 IP65
HeightMax. 2000m
Electrical Characteristics
Supply15-35V DC or 10-25V AC
Power Consumption7VA
External ConnectionsPlug-in terminals
ScaleTemperature: -40...125 °C
Humidity: 0.0%...100.0%
Accuracy±2 RH% (20...80% for RH range)
±4 RH% (0...100% for RH range)
±0.5 °C (for 20...40 °C range)
±1 °C (for 0...70 °C range)
±2 °C (for -40...125 °C range)
Response Time63% humidity variation for 7s (with 1m/s airflow at 25 °C)
63% temperature variation for 20s (with 1m/s airflow at 25 °C)
Output
Analog Output0-20mA DC or 0-10V DC selectable on device
Housing
Mounting MethodWall mounting
DimensionsL137xW58xH35 mm
Immersion Length50 mm
WeightApprox. 125g (after packaging)
Enclosure MaterialSelf extinguishing plastics
Looks like you don't speak Turkish. Would you like to view this content in English? Yes, please No