0...100 RH% humidity measurement
-40...125 °C temperature measurement
Selectable 0-20mA or 0-10V output
Duct type mounting
Communication via RS-485 ModBus protocol (order option)
CE marked according to European Norms
Environmental Conditions | |
Ambient/Storage Temperature | -40...50 ºC |
Protection Degree | According to EN 60529 IP65 |
Height | Max. 2000m |
Electrical Characteristics | |
Supply | 90-250V AC, 50/60Hz or 9-30V DC / 7-24V AC, 50/60Hz SMPS |
Power Consumption | 2VA |
External Connections | Plug-in terminals |
Scale | Temperature: -40.0...125.0 °C Humidity: 0.0%...100.0% |
Accuracy | ±2 RH% (20...80% for RH range) ±4 RH% (0...100% for RH range) ±0.5 °C (for 20...40 °C range) ±1 °C (for 0...70 °C range) ±2 °C (for -40...125 °C range) |
Response Time | 63% humidity variation for 7s (with 1m/s airflow at 25 °C) 63% temperature variation for 20s (with 1m/s airflow at 25 °C) |
Output | |
Analog Output | 0-20mA DC or 0-10V DC selectable on device |
Housing | |
Mounting Method | Duct type mounting |
Immersion Length | 150, 250, 350 mm |
Weight | EHTS-DC-xV-150: Approx. 500g (after packaging) EHTS-DC-xV-250: Approx. 550g (after packaging) EHTS-DC-xV-350: Approx. 615g (after packaging) |
Enclosure Material | Self extinguishing plastics |