ECVC
  • Can be used with current transformer or shunt

  • Measuring type can be selected as AC, DC or True RMS

  • Configurable mA and V outputs

  • Three-way isolation between input, output and power supply

  • Communication feature via RTU

  • Rail mounted

  • Plug-in terminals connection

  • CE marked according to European Norms

Manuals

Environmental Conditions
Ambient/Storage Temperature0...50 ºC / -25...70 ºC
Relative Humidity80% relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C
Protection DegreeIP 20 According to EN60529
HeightMax. 2000m
Electrical Characteristics
Inputs0-100V AC/DC (device may be damaged at ±500V DC and above voltages)
0-500V AC/DC (device may be damaged at ±1250V DC and above voltages)
Input Impedances0-100V AC/DC input: 176.8kohm
0-500V AC/DC input: 884kohm
Frequency RangeAC , 10Hz-200Hz (10Hz-70Hz for square wave form)
Sampling Time250ms
A/D Converter12 bit
D/A Converter12 bit
Output0-20mA DC, 4-20mA DC, 0-10V DC or 1-5V DC selectable (load resistance for current outputs up to 500ohm)
AccuracyAC: ±1% (±2% for square wave form)
DC: ±1%
RMS: ±1% (±2% for square wave form)
SupplyECVC-UV: 90-250V AC, 50/60Hz
ECVC-LV: 9-30V DC or 7-24V AC, 50/60Hz
Power ConsumptionMax. 7VA
External ConnectionsPlug-in terminals
Housing
Mounting MethodTH35 or G-32 rail mounting
DimensionsW25xH97xD115 mm
WeightApprox. 150g (after packaging)
Enclosure MaterialSelf extinguishing plastics