Can be used with current transformer or shunt
Measuring type can be selected as AC, DC or True RMS
Configurable mA and V outputs
Three-way isolation between input, output and power supply
Communication feature via RTU
Rail mounted
Plug-in terminals connection
CE marked according to European Norms
Environmental Conditions | |
Ambient/Storage Temperature | 0...50 ºC / -25...70 ºC |
Relative Humidity | 80% relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C |
Protection Degree | IP 20 According to EN60529 |
Height | Max. 2000m |
Electrical Characteristics | |
Inputs | 0-100V AC/DC (device may be damaged at ±500V DC and above voltages) 0-500V AC/DC (device may be damaged at ±1250V DC and above voltages) |
Input Impedances | 0-100V AC/DC input: 176.8kohm 0-500V AC/DC input: 884kohm |
Frequency Range | AC , 10Hz-200Hz (10Hz-70Hz for square wave form) |
Sampling Time | 250ms |
A/D Converter | 12 bit |
D/A Converter | 12 bit |
Output | 0-20mA DC, 4-20mA DC, 0-10V DC or 1-5V DC selectable (load resistance for current outputs up to 500ohm) |
Accuracy | AC: ±1% (±2% for square wave form) DC: ±1% RMS: ±1% (±2% for square wave form) |
Supply | ECVC-UV: 90-250V AC, 50/60Hz ECVC-LV: 9-30V DC or 7-24V AC, 50/60Hz |
Power Consumption | Max. 7VA |
External Connections | Plug-in terminals |
Housing | |
Mounting Method | TH35 or G-32 rail mounting |
Dimensions | W25xH97xD115 mm |
Weight | Approx. 150g (after packaging) |
Enclosure Material | Self extinguishing plastics |