ECTC
  • Configurable T/C, RTD and NTC inputs

  • Configurable mA and V outputs

  • Configurable scale

  • Ambient temperature compensation

  • 3-way isolation between the input, output and supply

  • Rail mounting

  • Plug-in terminals connection

  • CE marked according to European Norms

Manuals

Environmental Conditions
Ambient/Storage Temperature0...50 ºC / -25...70 ºC
Relative Humidity80% relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C
Protection DegreeIP 20 According to EN60529
HeightMax. 2000m
Electrical Characteristics
Output0-20/4-20mA DC (max. load resistance 500ohm)
0-10/1-5V DC selectable from the device
SupplyECTC-UV:90-250V AC ± 10%, 50/60Hz
ECTC-LV: 9-30V DC/7-24V AC ± 10%, 50/60Hz
Power ConsumptionMax. 7VA
Line ResistanceFor thermocouple max. 100ohm, for 3 wired PT100 max. 20ohm
A/D Converter10 bit
D/A Converter12 bit
External ConnectionsPlug-in terminals
InputsPT100 Resistance thermometer -100...600 °C
NTC -50...150 °C
J (Fe-Const) Thermocouple 0...600 °C
K (NiCr-Ni) thermocouple 0...1200 °C
S (PT10Rh-Pt) thermocouple 0...1600 °C
R (PT13Rh-Pt) thermocouple 0...1600 °C
Accuracy0.5% ± 1
Housing
Mounting MethodTH35 or G-32 rail mounting
DimensionsW25xH97xD97 mm
WeightApprox. 150g (after packaging)
Enclosure MaterialSelf extinguishing plastics