Configurable T/C, RTD and NTC inputs
Configurable mA and V outputs
Configurable scale
Ambient temperature compensation
3-way isolation between the input, output and supply
Rail mounting
Plug-in terminals connection
CE marked according to European Norms
Environmental Conditions | |
Ambient/Storage Temperature | 0...50 ºC / -25...70 ºC |
Relative Humidity | 80% relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C |
Protection Degree | IP 20 According to EN60529 |
Height | Max. 2000m |
Electrical Characteristics | |
Output | 0-20/4-20mA DC (max. load resistance 500ohm) 0-10/1-5V DC selectable from the device |
Supply | ECTC-UV:90-250V AC ± 10%, 50/60Hz ECTC-LV: 9-30V DC/7-24V AC ± 10%, 50/60Hz |
Power Consumption | Max. 7VA |
Line Resistance | For thermocouple max. 100ohm, for 3 wired PT100 max. 20ohm |
A/D Converter | 10 bit |
D/A Converter | 12 bit |
External Connections | Plug-in terminals |
Inputs | PT100 Resistance thermometer -100...600 °C NTC -50...150 °C J (Fe-Const) Thermocouple 0...600 °C K (NiCr-Ni) thermocouple 0...1200 °C S (PT10Rh-Pt) thermocouple 0...1600 °C R (PT13Rh-Pt) thermocouple 0...1600 °C |
Accuracy | 0.5% ± 1 |
Housing | |
Mounting Method | TH35 or G-32 rail mounting |
Dimensions | W25xH97xD97 mm |
Weight | Approx. 150g (after packaging) |
Enclosure Material | Self extinguishing plastics |